Pressure Controller
Installation and Operation Manual
All safety regulations, local
codes and instructions that appear in the manual or on the equipment must be
observed to ensure personal safety and to prevent damage to either the controls
or the equipment connected to it. If the equipment is used in a manner not
specified by the manufacturer the protection of it and personnel may be
impaired.
The Electrical Power Supply
requirements are: 220v, 1phase, 60hz, 20amp
The supply should be from a dedicated circuit that can be switched OFF and locked when the Pressure Controller is not used or is being serviced. Connect the power supply to fuses 1-FU ,2-FU and Ground. Refer to the electrical schematic for exact wiring information.
Mount the Cabinet to a
suitable vertical surface. The Cabinet location should provide easy operator
access and visibility to the door mounted operator controls.
The junction box contains the
wiring for the pressure controller servomotor, and pressure ram overtravel
limit switches. A cable connects the junction box to the Main Electrical Cabinet.
The cable wiring connects to a receptacle on the side of the Main Electrical
Cabinet.
A pressure Transducer is
connected to the ram output pressure supply line. The transducer provides an
electronic (4-20 ma) signal that is proportional to the actual hydraulic
pressure. A cable from the Main Electrical Cabinet has an attached connector
that plugs into the transducer. A calibration record is provided with the
transducer and should be kept with the system.
The electrical wiring is now
completed.
Operator Controls Description
[POWER, PULL ON-PUSH OFF] PUSH BUTTON
Pulling this push button
energizes the electrical controls. The red light is ÒonÓ when the controls are
energized. Pressing this push button de-energizes the electrical controls. The
push button will light when the controls are energized.
[PRESSURE/ DEC-INC] 3
position Selector switch
Selects the direction of
pressure change in the manual operation mode.
Select the [INC] position to
increase the system pressure. The system pressure will increase to the Omega
Setpoint [1] value.
Select the [DEC] position to
decrease the system pressure. The system pressure will decrease to zero TONS
pressure. The controls will not permit the pressure to be a negative value.
Select the middle position to
stop system pressure change.
Note: The effect of the experiment may cause the ÒactualÓ pressure to change in the system. The selector switch acts to set the system pressure to an initial value. The actual experiment may cause the system pressure to raise or lower from the initial setting. Should the experiment cause the ÒactualÓ pressure to exceed the Omega Setpoint [2] value, the pressure will be lowered automatically until Setpoint [2] is reached.
[RPM] digital meter
This meter indicates the
pressure ram motor operating speed (0-2,000 RPM) and pressure direction (+) or
(-). The operating speed of the motor determines the rate of pressure change in
the system. The pressure (increase and decrease) rate is adjustable by the
[PRESSURE ADJ] 10-turn potentiometer.
[PRESSURE ADJ] 10-turn potentiometer
Controls the speed of the
pressure ram motor. The motor speed determines the rate of pressure change
(increasing or decreasing) in the system. The motor speed can be adjusted from
0-2,000 RPM. Turn the control clockwise to increase the motor speed. Turn the
control counterclockwise to decrease the motor speed. The system pressure rate
is dependent upon the actual experiment. Set the control to an initial position
to determine a system rate, then adjust the control to the rate desired.
[BYPASS/ DEC-INC]
selector switch, 2 position keyed
This
selector switch allows the operation of the pressure ram should the controls
fault after reaching either end of the ram stroke. If the system pressure ram
reaches either end of its stroke the controls will stop the ram, the [POWER ON]
light will turn off and the red [OVER TRAVEL FAULT] pilot light turns on.The
pressure ram can only be reversed from itÕs overtravel position by using the
[BYPASS/DEC-INC] selector switch.
To correct a fault condition:
Turn the [PRESSURE/
DEC-INC] selector switch to
the middle position
Turn the [BYPASS/ DEC-INC] switch
to the [INC] position to advance the ram if it faulted in the
retracted direction.
Turn the switch to the [DEC]
position to retract the ram if it faulted in the advance direction.
The ram can only be moved in
the direction to correct the fault. When the fault has been corrected the [OVERTRAVEL
FAULT] pilot light will turn off and the pressure
controls can be energized.
OMEGA PRESSURE METER
Note: Refer to the Omega
Operators Manual for detailed instructions on the operation and use of the
Omega controller.
The Omega Pressure Controller displays the actual system pressure in TONS (0-1,000.0). A Pressure transducer that is connected to the press hydraulic system provides a 4-20 milliamp electronic signal to the controller. This pressure signal is also connected to the PLC.
There are two- (2) user
adjustable Setpoints on the Omega pressure controller that are used to control
the system pressure. They are called ÒSP1Ó and ÒSP2Ó (note: ÒSP3Ó and ÒSP4Ó are
not used).
The setpoint is actuated when
the ÒactualÓ pressure reading reaches the setpoint value. The setpoints have
status indicators located on the pressure reading display. The indicator is
light is ÒonÓ The display flashes when the actual value reaches the setpoint value.
To view the ÒSetpointÓ values
press the [SETPTS] button on the controller. The controller now displays the
Setpoint value and indicates what setpoint is being shown. The Setpoint can be
changed by pressing the [MIN] and the [MAX] buttons. Each time the [SETPTS]
button is pressed the controller saves the displayed Setpoint and then steps to
the next Setpoint. Press the [RESET] button to return to the controller to
display the ÒactualÓ pressure reading. During normal operation the controller
should be set to display the ÒactualÓ pressure.
Setpoint one (1)
Setpoint [SP1] is the Low-pressure
limit. Pressure increase is stopped when the ÒactualÓ pressure is at (or
above) the ÒSetpoint 1Ó value.
If ÒactualÓ pressure is above
ÒSetpoint one (1)Ó a numeral "SP1" will be illuminated on the meter.
Setpoint two (2)
Setpoint [SP2] is the High
pressure limit. If the ÒactualÓ pressure rises to (or above) Setpoint [2] a
numeral "2" will be illuminated. The system pressure will
automatically be decreased until the ÒactualÓ reading is less than the value of
setpoint 2. The display flashes when setpoint two (2) limit is active.
Example:
Setpoint one (1) programmed limit (500.0 Tons)
Setpoint two (2) programmed limit (505.0 Tons)
Turn the [DEC-INC] selector switch to the [INC]
position.
The controller will increase pressure to (500.0
Tons), then stop. If the actual pressure drops to (499.9 Tons), the controller
will energize to increase the system pressure.
If the experiment causes the system pressure to
reach (505.0 Tons) the controls will react by decreasing the system pressure to
(504.9 Tons).
CUSTOMER SERVICE and SUPPORT
Rockland Reasearch
Phone: (914) 353-4686
Fax: (914) 358-9119
Internet: http://Rocklandresearch.com
E-mail: petermc@Rocklandresearch.com
Industrial Automation Specialists, Inc
321 North St.
Goshen, CT 06756
Phone: 860-491-9535
Fax: 860-491-9537
E-mail: